Hussmann HGL-2-BS Commercial Refrigerator Questions & Answers
Compressor working condencer not getting
Hi,
In this case you probably have a leak and have los the charge in the unit...
Many times a freezer and/or refrigerator do not work right because of a dirty condenser coil...there are also many other things that can go wrong.
If you are hearing a clicking or buzzing then check out the last two tips.
If your refrigerator is running but warm, then...
Check out these tips that I wrote about that... it is a great place to start trouble shooting your unit...and something that you can do rather then calling a repair person to do a simple thing for you...
Refrigerator Condenser Coil Cleaning Refrigerator Repair
Refrigerator Troubleshooting Refrigerator Compressor
Refrigerator Compressor Start Capacitor and Start Relay
Refrigerator or Freezer not Cooling or Getting Cold
heatman101
12/4/2010 2:58:01 PM •
Hussmann...
•
Answered
on Dec 04, 2010
I have a Hussman 6x9
Assuming the compressor is sized correctly( and usually they are) There are a couple of fairly easy things to check.
1.) The compressor unit.
Are the fan(or fans ) operating. Some units have two condenser fans and will operate with only one until the temperature gets too high for it to keep up.
Is the coil clean. A dirty coil can cause unit to fail too keep up in high temperatures.
2.) The evaporator unit .
Same as condenser unit . Are the fans all working
Are the coils clean.
3.) Defrost Timer. Is the time set correctly .
Is the unit defrosting during low usage time periods.
Hope this helps
Bob
1/26/2018 8:18:53 PM •
Hussmann...
•
Answered
on Jan 26, 2018
I have a Hussman display
first of all, there was a reason why the old compressor locked up and without finding out the reason why the problem is following the new one. The hissing that you are talking about is it coming from the compressor? If it is it sound like it is the internal pressure relief going off, this noise should come and go. Yes you do have a problem, and it could be a number of reasons but you need to find out the right one or you will spend more money than it would have cost a service man to repair, at least if he did it you could go back to him.
1. Was compressor burnt at time of lockup?
2. did you change the drier?
3. is it correctly charged?
4. Is TXV feeding properly?
let me know and maybe i can help.
8/28/2011 2:55:50 PM •
Hussmann...
•
Answered
on Aug 28, 2011